IO Module Configuration and Status
This section defines the Configuration parameters in the CODESYS IDE (if configuration is required) for each module and any associated status signals.
Status signals could be for the module as a whole e.g. Missing 24V or for an individual IO Channel basis e.g. UnderRange.
Discrete Input
The following modules are for Discrete (On/Off) type of modules.
P2-08ND3-1
This module supports up to eight(8) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16ND3-1
This module supports up to sixteen(16) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-32ND3-1
This module supports up to thirty-two(32) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-08NE3
This module supports up to eight(8) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16NE3
This module supports up to sixteen(16) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-32NE3
This module supports up to thirty-two(32) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-08NAS
This module supports up to eight(8) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16NA
This module supports up to sixteen(16) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16ND-TTL
This module supports up to sixteen(16) Discrete input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
Discrete Output
The following modules are for Discrete (On/Off) Output type of modules.
P2-08TD1S
This module supports up to eight(8) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-08TD2S
This module supports up to eight(8) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-08TD1P
This module supports up to eight(8) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-16TD1P
This module supports up to sixteen(16) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-32TD1P
This module supports up to thirty-two(32) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-08TD2P
This module supports up to eight(8) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-16TD2P
This module supports up to sixteen(16) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-32TD2P
This module supports up to thirty-two(32) Discrete Input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Channel:
- Fault Output
Output signal (by channel) is the fault state of overload.
If
TRUE
, the channel is in an over current state.If
FALSE
, the channel is operating with range.
P2-15TD1
This module supports up to fifteen(15) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-15TD2
This module supports up to fifteen(15) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-08TAS
This module supports up to eight(8) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16TA
This module supports up to sixteen(16) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
P2-16TD-TTL
This module supports up to sixteen(16) Discrete Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
Analog Input
These modules are input only devices that are either Current, Voltage or both Current/Voltage types.
P2-04AD
This module supports up to four(4) of both Current and Voltage input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 4 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Channel Range
- Ch1 Range, Ch2 Range, Ch3 Range, Ch4 Range
Each channel is individually configurable.
+/-5V
,+/-10V
,0-5V
,0-10V
,0-20mA
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-04AD-1
This module supports up to four(4) Current input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 4 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-08AD-1
This module supports up to eight(8) Current input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-16AD-1
This module supports up to sixteen(16) Current input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Ch. Select 1-9
,Ch. Select 1-10
,Ch. Select 1-11
,Ch. Select 1-12
Ch. Select 1-13
,Ch. Select 1-14
,Ch. Select 1-15
,Ch. Select 1-16
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-08ADL-1
This module supports up to eight(8) Current input (12-bit resolution) signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-16ADL-1
This module supports up to sixteen(16) Current input (12-bit resolution) signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Ch. Select 1-9
,Ch. Select 1-10
,Ch. Select 1-11
,Ch. Select 1-12
Ch. Select 1-13
,Ch. Select 1-14
,Ch. Select 1-15
,Ch. Select 1-16
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-04AD-2
This module supports up to four(4) Voltage input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 4 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-08AD-2
This module supports up to eight(8) Voltage input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-16AD-2
This module supports up to sixteen(16) Voltage input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Ch. Select 1-9
,Ch. Select 1-10
,Ch. Select 1-11
,Ch. Select 1-12
Ch. Select 1-13
,Ch. Select 1-14
,Ch. Select 1-15
,Ch. Select 1-16
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-08ADL-2
This module supports up to eight(8) Voltage input (12-bit resolution) signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-16ADL-2
This module supports up to sixteen(16) Voltage input (12-bit resolution) signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Ch. Select 1-9
,Ch. Select 1-10
,Ch. Select 1-11
,Ch. Select 1-12
Ch. Select 1-13
,Ch. Select 1-14
,Ch. Select 1-15
,Ch. Select 1-16
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
Analog Output
P2-04DA
This module supports up to four(4) of both Current and Voltage output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Channel Range
- Ch1 Range, Ch2 Range, Ch3 Range, Ch4 Range
Each channel is individually configurable.
+/-10V
,4-20mA Source
,4-20mA Sink
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-04DA-1
This module supports up to four(4) Current output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-08DA-1
This module supports up to eight(8) Current output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-16DA-1
This module supports up to sixteen(16) Current output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-04DAL-1
This module supports up to four(4) Current output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-08DAL-1
This module supports up to eight(8) Current output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-16DAL-1
This module supports up to sixteen(16) Current output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-04DA-2
This module supports up to four(4) Voltage output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-08DA-2
This module supports up to eight(8) Voltage output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-16DA-2
This module supports up to sixteen(16) Voltage output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-04DAL-2
This module supports up to four(4) Voltage output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the Module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-08DAL-2
This module supports up to eight(8) Voltage output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
P2-16DAL-2
This module supports up to sixteen(16) Voltage output signals (12-bit resolution).
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.
Analog Combo
The Combo modules support both Inputs and Outputs.
P2-8AD4DA-1
This module supports both input and output Current signals. Up to eight(8) inputs and four(4) outputs.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Channel Resolution
- Input Ch1 Resolution - Input Ch8 Resolution
Each channel is configurable for resolution (Coarse-12bit/Medium-14bit/Fine-16bit)
Coarse
,Medium
,Fine
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-8AD4DA-2
This module supports both input and output Voltage signals. Up to eight(8) inputs and four(4) outputs.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Channel Range
- Input Ch1 Range - , Input Ch2 Range
Each channel is individually configurable.
0-5V
,0-10V
Channel Resolution
- Input Ch1 Resolution - Input Ch8 Resolution
Each channel is configurable for resolution (Coarse-12bit/Medium-14bit/Fine-16bit)
Coarse
,Medium
,Fine
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Missing 24V
External 24V power being applied or absent.
If
TRUE
, the module does not have the 24V field power within specification connected.If
FALSE
, the module has 24V applied within specification.Channel:
- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
Temperature
The following modules are used to measure temperature in a variety of applications.
P2-08THM
This module supports up to eight(8) Temperature or Voltage input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Channel Range
- Range Ch1 - Range Ch8
Each channel is individually configurable.
Thermocouples:
Type J
,Type K
,Type E
,Type R
,Type S
,Type T
,Type B
,Type N
,Type C
Voltage:
0-39mV
,+/-39mV
,+/-78mV
,0-156mV
,+/-156mV
,0-1.25V
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.Burnout Enable/Temperature Scale
- (various, see below)
If
Disable Burnout Detection/Deg C
, Burnout OFF and Temp scale Celsius.If
Low Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
High Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
Disable Burnout Detection/Deg F
, Burnout OFF and Temp scale Fahrenheit.If
Low Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.If
High Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Module Not Ready
First channel data conversions after a power-up or reconfiguration are not ready.
If
TRUE
, the module has not processed the channel inputs yet.If
FALSE
, current channel input data reflects latest configuration.Channel:
- Burnout Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-08NTC
This Thermistor module supports up to eight(8) Temperature input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1- 8 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
,Ch. Select 1-7
,Ch. Select 1-8
Burnout Enable/Temperature Scale
- (various, see below)
If
Disable Burnout Detection/Deg C
, Burnout OFF and Temp scale Celsius.If
Low Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
High Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
Disable Burnout Detection/Deg F
, Burnout OFF and Temp scale Fahrenheit.If
Low Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.If
High Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.Channel Range
- Range
The range selected applies to the all the module inputs.
Thermistor Type:
2252
,10K-AN
,10K-CP
,5K
,3K
,1.8K
,Digital Conversion Filter
- Digital Filter
The speed at which the Converter runs. Faster speed is lower accuracy.
Sample Rate:
61ms
,16ms
,4ms
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Module Not Ready
First channel data conversions after a power-up or reconfiguration are not ready.
If
TRUE
, the module has not processed the channel inputs yet.If
FALSE
, current channel input data reflects latest configuration.Channel:
- Burnout Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel sensor is open and not functioning.If
FALSE
, the channel sensor is operating correctly.- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
P2-06RTD
This RTD module supports up to six(6) Temperature or Resistance input signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Number of Channels Active:
- Ch. Select
Selects between 1-6 active input channels.
Ch. Select 1
,Ch. Select 1-2
,Ch. Select 1-3
,Ch. Select 1-4
Ch. Select 1-5
,Ch. Select 1-6
Burnout Enable/Temperature Scale
- (various, see below)
If
Disable Burnout Detection/Deg C
, Burnout OFF and Temp scale Celsius.If
Low Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
High Side Burnout Detection/Deg C
, Burnout ON and Temp scale Celsius.If
Disable Burnout Detection/Deg F
, Burnout OFF and Temp scale Fahrenheit.If
Low Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.If
High Side Burnout Detection/Deg F
, Burnout ON and Temp scale Fahrenheit.Channel Range
- Range
The range selected applies to the all the module inputs.
RTD Type:
jPt100
,Pt100
,Pt1000
,Cu10
,Cu25
,Ni120
,Resistance:
0-10K
,0-6.25K
,0-3.125K
,0-1562.5K
,0-781.25
,0-390.625
,0-193.3125
Digital Conversion Filter
- Digital Filter
The speed at which the Converter runs. Faster speed is lower accuracy.
Sample Rate:
16ms
,28ms
,56ms
,75ms
,88ms
,488ms
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.- Module Not Ready
First channel data conversions after a power-up or reconfiguration are not ready.
If
TRUE
, the module has not processed the channel inputs yet.If
FALSE
, current channel input data reflects latest configuration.Channel:
- Burnout Errors
Input signal (by channel) sensor is opened up and not functioning.
If
TRUE
, the channel sensor is open and not functioning.If
FALSE
, the channel sensor is operating correctly.- Under Range Errors
Input signal (by channel) is below the allowable input range.
If
TRUE
, the channel input is too low.If
FALSE
, the channel input is within range.- Over Range Errors
Input signal (by channel) is above the allowable input range.
If
TRUE
, the channel input is too high.If
FALSE
, the channel input is within range.
Relay Output
The Relay modules provide surge-protected outputs to operate DC or AC rated devices (6-24 VDC / 6-120 (or 6-240) VAC).
P2-08TRS
This module supports up to eight(8) Relay Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-16TR
This module supports up to sixteen(16) Relay Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
P2-06TRS
This module supports up to six(6) Relay Output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)
Other
The following are specialty modules that do not fall under the previous categories.
P2-04PWM
This PWM module supports up to four(4) high speed output signals.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Channel Output Type
- Ch1 Output Type - Ch4 Output Type
The output type is channel configurable and deals with PWM speed and direction.
PWM Type:
PWM (x1)
,PWM (x0.1)
,PWM (x0.01)
Direction:
Dir
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the Module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
Module:
- Module Failed
Catastrophic failure state of the module.
If
TRUE
, the module has a major failure and is unusable.If
FALSE
, the module is operating normally.
P2-08SIM
The P2-08SIM Input Simulator module provides 8 toggle switches to simulate input devices.
Configuration is found in the Parameters section of the IO Module.
Status is found in the IO Mapping section of the IO Module.
Configuration
The following items can be configured:
Hot Swap Enable
- True/False
Module allowed to be removed.
If
TRUE
, the module can be removed and the system will not go into Stop mode. Task operations continue.If
FALSE
, removing the module will put the system into Stop mode.
Status
The following items give the specific status of the module and each channel:
(No status signals for this module)